EasyManua.ls Logo

Festo Controller CECC-S - Configuring Modbus TCP; CECC as a Modbus TCP Master

Festo Controller CECC-S
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Festo Controller CECC
48
4.10.3 Scanning for an IO-Link device
Instead of manually selecting an IO-Link device, you can also have Codesys find it by scanning.
Prerequisites:
There is a (temporary) connection to the device via the active path.
CODESYS V3 pbF has been logged into the device at least once ( section "Online mode").
1. Highlight the "IO-Link Master" branch in the CODESYS V3 pbF device window.
Figure: Device window - selecting "IO-Link Master"
2. Open the "Scan Device" dialog
menu command [Project] [Scan for Devices] or
context menu [Scan for Devices].
3. Note the safety prompt about connected actuators at the IO-Link master ports. If you answer "Yes", a
dialog for scanning for connected IO-Link devices opens.
Figure: "Scan Devices" at the IO-Link master ports
4. Check the "show differences to project" box to show the IO-Link configuration of the Codesys project
in parallel.
5. Click the "Copy all devices to project" button to transfer the read-in configuration to the Codesys
project.

Table of Contents

Related product manuals