B. Supplementary information
B−6
Festo P.BE−MTR−DCI−IO−EN en 0606b
Permitted value ranges Transferred parameters and values are checked by the
MTR−DCI before being accepted.
Non−permitted parameters will not be accepted.
Values outside the permitted value range will be limited
to the next valid value.
Please note
In the case of non−permitted parameters or values, no fault
message will appear in the reply, the value transferred will
always be returned.
Recommendation:
· Check that values and parameters have been written
correctly by downloading the current contents of the
parameter or value with one of the following Read
commands:
Transmission faults If there are transmission faults between the Host (PC) and the
target device, e.g. due to faults in the Host command, Object
2FF0:FF<CR> will be transferred instead
of the regular reply.
Possible causes:
incorrect starting character, separating character or
empty character
incorrect hex figure
incorrect value type.
Name
Class IIII SS Type Acc
communication_
error
Var 2FF0 00 UINT16 R
Value Comment
0xFF In the case of a transmission fault, the value <0xFF>
will be transferred instead of the regular reply.