17
LOAD
Rly1 Rly2 Rly3 Rly4 Rly5 Rly6 Rly7 Rly8
51 61 48 58 35 43 33 41 32 40 26 27 2 25 15 1 24 14 70 55 54 53 45 44 36 28 56 46 38 37 30 29
DISCRETE INPUT 1
DISCRETE INPUT 2
DISCRETE INPUT 3
DISCRETE INPUT 4
DISCRETE INPUT 5
DISCRETE INPUT 6
DISCRETE INPUT 7
DISCRETE INPUT 8
BATTERY (+)
69
65
52
BATTERY (-)
DISCRETE SINKING OUTPUT 1
SYSTEM
BATTERY
12 or 24 VDC
RELAY OUTPUTS
(NOTE A)
PASSIVE ANALOG 1 (+)
PASSIVE ANALOG 1 (-)
PASSIVE ANALOG 2 (+)
PASSIVE ANALOG 2 (-)
PASSIVE ANALOG 3 (+)
PASSIVE ANALOG 3 (-)
POWERWIZARD 2.1
LCD DISPLAY
13 11 9 7 31 47 57 39 50 34 42 62 64 63 5 3 4 67 66
V A
V B
V C
NEUTRAL
0-600 VAC
RMS
I A
I B
I C
I COMMON
MODBUS
DATA LINK
J1939 CAN DATA LINKS
0-5A AC
RMS
CAN 1 DATA LINL (+)
CAN 1 DATA LINL (-)
CAN 1 SHIELD
CAN 2 DATA LINL (+)
CAN 2 DATA LINL (-)
CAN 2 SHIELD
MODBUS (+)
MODBUS (-)
MODBUS REF
MPU
MAGNETIC PICKUP INPUT (-)
MAGNETIC PICKUP INPUT (+)
+12 or +24 VDC
NOTE (B)
L1
L2
L3
N
NOTE A: Load are not to exceed 2A of current draw
(Minimum current 10mA)
NOTE B: Load are not to exceed 300 mA of current draw
CT A
CT B
CT C
5V output
16
Figure 7 : PowerWizard 2.1 Control Electrical Connections
4.4 Winding Connections
The wiring connections between the generating set and PowerWizard depend on the winding congurations of the generator.
Refer to the following connection diagarms.
Phase A
Phase B
Phase C
Nuetral
13
11
9
7
Figure 8: Three phase 4-wire (series or parallel) star
Phase A
Phase B
Phase C
Nuetral
13
11
9
7
Figure 9: Three phase 4-wire Delta