7.4 Disabling NOT IN AUTO
By default PowerWizard control panels have a generating set “not in auto warning. This warning will be active when the control
is in ‘STOP’ or ‘RUN’ mode. For certain applications it may be suitable to disable this warning. To disable “Not In Auto perform the
following.
MAIN MENU > CONFIGURE > SETPOINTS > EVENTS > EVENT RESPONSE CONFIGure OTHER SYSTEM CONFIG
Scroll to "Gen Control Not in Auto Warning Cong"
Select edit by using left cursor key and then press Enter
This takes you to the screen that is used to congure the desired response for the "Not In Auto" alarm. The options available can
be viewed or edited.
A indicates which options are selected. The user may select or remove by using the left cursor key. If unable to EDIT check
that the generating set is in STOP position and that the required password level is used.
7.5 Disabling Thermo Start (Start Aid Activation)
To disable the Thermo Start go to the “START AID ACTIVATION TIME” screen as shown below:
MAIN MENU > CONFIGURE > SETPOINTS > CONTROL > AUTO START/STOP
Press enter and then scroll down till you come to the “START AID ACTIVATION TIME” screen.
Once at this screen, set the time to 0 seconds.
ENTER
VIEW
WARNING
AUDIBLE ALERT
ACTIVE ONLY