48
1.6 Network
Setpoints > Network > Data Link - SCADA
Setpoint Name
Min
Value
Max Value Units Description
SCADA Data Link Baud Rate 2400 57600 N/A
SCADA Data Link Parity N/A N/A N/A Select “None” “Odd” or “Even”
SCADA Data Link Slave Address 1 247 N/A
SCADA Data Link Access Password 0.0 0xf N/A
SCADA Data Link Connection Timeout Interval 0.1 3600.0 sec.
RS-485 Bias Resistor Enable Status Disabled Enabled N/A
1.7 Reduced Power Mode
Setpoints > Reduced POWER Mode > Delay Time
Setpoint Name
Min
Value
Max
Value
Units Description
Reduced power mode delay time 1 100 min
The control will run at reduced power mode
after delay. This mode can be disabled using
Level 3 password.