3.2 Wiring
Power supply must be connected to the terminal block.
3.2.1 Power jumper settings
The QuickServer Carrier Board power jumper is set to position A by default, but can be changed to position B for
other power supply requirements:
A Position : The Carrier makes use of a full-wave rectifying bridge. Can be used for 12-24 VAC input or 9 30 VDC
input. At 9 VDC this becomes marginal.
B Position : The Carrier makes use of a half-wave rectifying bridge. Best position for Grounded AC Transformers
and for using DC voltage down to 9VDC.
Power Jumper Switch
in “A” position