EasyManua.ls Logo

Fiessler ULVT - Response Time (Examples); Safety Distance (Example)

Default Icon
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.5 Response times of cascaded light grids
The cascadable light grids detect any interruption of the protection field of the secondary (="slave") sensor wit-
hin 3ms. The response time of the respective light grids is obtained by adding the individual response time to 3ms for
each preceeding light grids.
Master sensor individual response time (as shown on the type plate)
Slave sensor1 individual response time + 3 ms
Slave sensor2 individual response time + (2 x 3 ms = 6 ms)
The own response time is stated oon the type plate of the respective light grid.
The table on page 13 shows the individual response times for all standard light grids.
8 Cascading of Light Grids -Response times / Safety distances
Table 35/1 response times cascadable light curtains
example:
response times
Master sensor
ULVTK 500/65
Slave sensor1
ULVTK 500/35
9 ms
7 ms + 3 ms = 10 ms
Slave sensor2
ULVT 800/3
4 ms + 6 ms = 10 ms
Resolution
see tables page 13
individual response
time of the light grid,
see tables page 13
calculated
response time
safe distance
(Formula: refer to chapter
4.2.1)
Master sensor
ULVTK 500/65
slave sensor 1
ULVTK 1500/195
14 mm (C= 0 mm)
14 mm (C= 0 mm)
10 ms
21 ms
same as individual re-
sponse time= 10 ms
21 ms + 3 ms = 24 ms
S = 170 mm
S = 198 mm
slave sensor 2
ULVT 500/35
30 mm (C= 128 mm)
7 ms
7 ms + 6 ms = 13 ms
S = 176 mm + 128 mm =
304 mm
Tabllelle 35/2 calculation example safe distance of cascaded light grids
Table for calculating of the respective response times of your utilized cascaded light grids :
resolution
s. tables S. 13
individual response
time of the light grid,
see tables page 13
calculated response
time
safe distance
(Formula: refer to chap-
ters 4.2.1, 4.2.2. or 4.2.3)
Master sensor
Slave sensor 1
....... +3 ms =
S = ..............mm
S = .............. mm
Slave sensor 2
....... +6 ms =
S = ..............mm
Tabelle 35/3
8.6 safe distance of cascaded light grids
When calculating the safe distance of the light grids (refer to chapter 4.2), it must be considered that each preceding light
grid will increase the response time of the cascaded light grid by 3ms.
Calculation example:
FIESSLER
E L E K T R O N I K
35
Fiessler Elektronik GmbH & Co. KG
Doku Nr. 958 Stand 22.01.2018 RK
Phone: +49 (0) 711 / 91 96 97-0 Internet: http://www.fiessler.de
Fax : +49 (0) 711 / 91 96 97-50 eMail: info@fiessler.de

Table of Contents