60 MS-9600LS Series Manual — P/N 52646:B8 11/20/2015
Installation Optional Modules and Devices
any addressable SLC input device (module, detectors) with any of the speaker circuits. In addition
1 of 14 (1 of 5 using the legacy ACC panel) can be generated over the selected speaker circuit. Any
fault in the ECC-50/100 audio system is sent to the FACP via the FACP Data Bus and is indicated
as an annunciator fault on the FACP display. A fault at the ACC-25/50ZS Series panel will cause
the FACP to indicate a System Trouble and the display will indicate a Voice Evac Fault.
For speaker circuit mapping and audio message assignment, refer to “Zone Message” on page 125.
Also, refer to “Programmed Activation by FACP” in chapter 3 of the ECC-50/100 Instruction Man-
ual (Doc. LS10001-000FL-E) or Appendix D, “Programmed Activation by FACP” in the ACC-
25/50ZS Series Instruction Manual (Doc. 51889).
Connect the ECC-50/100 panel’s FACP Data Bus at TB13 to TB9 on the FACP.
Figure 2.32 FACP Connection to ECC-50/100 Series Audio Panel
FACP
ECC-50/100
to other ACS/ANN
devices
A B
ANN
ACS
9600ecc.wmf