6 - ADVANCED PROGRAMMING MODE
6600 / 6665
6.5 PREVIOUS DAYS WATER USAGE (Pd):
Not viewed in timeclock regeneration mode.
Press the button. This display is identified by the letters “Pd”. This display shows the previous days water
usage recorded. This display is used as an aid in the valve maintenance and is not an option setting. The unit of
measure used depends on the display format chosen
(1)
.
Ex.: 28,4 m3(1) [Pd - - 28.4]
6.6 SYSTEM CAPACITY
Press the button . The unit of measure used depends on the display format chosen
(1)
. This display is used to
set the capacity of the softener. If required, the electronics will calculate a reserve. Adjust the value with the
and set buttons.
Ex.: Capacity 1200 m3° tH
(1)
: [- - - -1200]
6.7 REGENERATION CYCLE PROGRAMMING
to
The cycle 6 will not be viewed if the cycle 5 is cancelled [5 --- O F F ].
6.12 Press the button . The next displays are part of a series of option settings used to program the regeneration
cycles. Up to 6 cycles can be programmed. Each display is used to set the duration time (in minute) of that
cycle in the regeneration.
The first display in the series is regeneration cycle 1, example: Backwash
Ex.: - Cycle 1 (Backwash): 8 minutes [1 - - - 8.0]
- Cycle 4 (Brine refill): 8.4 minutes (8 min and 24 s.) [4 - - - 8.4]
6.13 CHLORINE CELL ACTIVATION (J):
Press the button . This display is identified by the letter “J”. This display is used to activate the chlorine
function during cycle 1.
Ex.: - No chlorinator installed [J- - - OFF]
- Chlorinator to turn on during the cycle 1 [J- - - - - -1]
6.14 CHLORINE CELL POWER DURATION
Press the button . This display is identified by the letter “dJ”. This display is used to set the chlorine cell
power on duration.
Note: During a regeneration with the chlorine cell set, for example cycle 2, the regeneration display
will show: [2C - - 38.2]
(1) The unit of measure depends on the display format chosen.
All examples above are based on the cubic meter format (see point 6.17).