6 - ADVANCED PROGRAMMING MODE
6600 / 6665
6.15 REGENERATION DAY OVERRIDE (A)
In timeclock regeneration mode, a value must be set.
Press the button .This parameter is identified by the letter “A”. This option is used to set the regeneration
day override option setting. This override setting determines the maximum amount of time (in days) the
softener can be in service without a regeneration, regardless of the volume of water used or the lack of a
sensor signal. The regeneration begins at the set regeneration time.
Ex.: - Override every 7 days [A - - - - - 7]
- Option cancelled [A - - - OFF]
6.16 VOLUME OVERRIDE (b)
Not viewed in time clock regeneration mode.
Press the button . This display is identified by the letter “b”. The volume override option is used to set the
maximum amount of water that can be used before a regeneration cycle is called for.
This option is typically used to bypass standard reserve or capacity calculations made by the electronics.
When this feature is used with meter delayed regeneration systems, it will be up to the installer to determine
a reserve capacity and subtract it from the calculated full capacity. The unit of measure depends on the
display format chosen
(1)
.
Ex.: Override every 2.6 m3(1) [b - - 2600]
6.17 DISPLAY FORMAT (U)
Press the button . This display is identified by the letter “U”. One of five following display
formats can be used. The current format used is the cubic meter (U4): the volume is in cubic
meter (m
3
), the flow rate in litre per minute (l/min), 24 hours timekeeping format, water hardness in French
degrees or °tH degrees and the sys-tem capacity in °tH degrees cubic meter (°tH x m
3
).
The format used for small volume is the litre (U2): the volume is in litre (l), the flow rate in litre per minute (l/
min), 24 hours timekeeping format, water hardness in French degrees or °Th degrees and the system capacity
in °tH degrees cubic meter (°tH x m
3
).
Ex.: - US format (not used) [U - - - - - 1]
- Litre format [U - - - - - 2]
- Standard metric (not used) [U - - - - - 3]
- Cubic meter format [U - - - - - 4]
Note: for further information, please contact our technical support.
6.18 VALVE TYPE (o)
Press the button. This parameter is identified by the letter “o”. This display is used to set the type of
valve used. The only possible settings are #1 and #2 for 6600 and 6700 valve family.
Ex.: - 6600 / 6665 [o - - - - - 1]
- 6700 / 6765 [o - - - - - 2]
(1) The unit of measure depends on the display format chosen.
All examples above are based on the cubic meter format (see point 6.17).