Program       Program 
Code Function Code  Description  Entry  Code 
 
10  Issue/Rev. 03 (8/97) 
022  A/C Input 4   Enter:  "00" No Assignment  (N/A)  022 
  Terminals 103 & 105    "01" Additive Feedback 1   (AFB1) 
      "02" Additive Feedback 2   (AFB2) 
      "03" Additive Feedback 3   (AFB3) 
      "04" Additive Feedback 4   (AFB4) 
      "05" Additive Feedback 5   (AFB5) 
      "06" Additive Feedback 6   (AFB6) 
      "07" Additive Feedback 7  (AFB7) 
      "08" Additive Feedback 8  (AFB8) 
      "09" First/Second High Flow  (FSC) 
      "10" Printer Tray Switch   (PTS)* 
      "11" Permissive 1 Contact   (PRC1) 
      "12" Permissive 2 Contact  (PRC2) 
      "13" Valve Power  (VPW) 
      "14" Valve Stem-Product 1  (VST1) 
      "15" Valve Stem-Product 2  (VST2) 
      "16" Valve Stem-Product 3  (VST3) 
      "17" Valve Stem-Product 4  (VST4)  __ __ 
 
*
Note:  Or can be used for Master Reset. 
 
Note:  For "Remote Start" operation either this code or code 028 must be programmed "11" (Permissive 1 Contact), code 807 must be 
programmed "5" ("Remote Start") and jumpers must be installed as shown in the Installation Manual (MN06064). 
 
 
023  A/C Input 5   Enter:  "00" No Assignment  (N/A)  023 
  Terminals 104 & 105    "01" Additive Feedback 1   (AFB1) 
      "02" Additive Feedback 2   (AFB2) 
      "03" Additive Feedback 3   (AFB3) 
      "04" Additive Feedback 4   (AFB4) 
      "05" Additive Feedback 5   (AFB5) 
      "06" Additive Feedback 6   (AFB6) 
      "07" Additive Feedback 7  (AFB7) 
      "08" Additive Feedback 8  (AFB8) 
      "09" First/Second High Flow  (FSC) 
      "10" Printer Tray Switch   (PTS)* 
      "11" Permissive 1 Contact   (PRC1) 
      "12" Permissive 2 Contact  (PRC2) 
      "13" Valve Power  (VPW) 
      "14" Valve Stem-Product 1  (VST1) 
      "15" Valve Stem-Product 2  (VST2) 
      "16" Valve Stem-Product 3  (VST3) 
      "17" Valve Stem-Product 4  (VST4)  __ __ 
 
*
Note:  Or can be used for Master Reset. 
 
Note:  For "Remote Stop" operation this code must be programmed "12" (Permissive 2 Contact), code 811 must be programmed "5" ("Remote 
Stop" and jumpers must be installed as shown in the Installation Manual (MN06064).