Program Program
Code Function Code Description Entry Code
10 Issue/Rev. 03 (8/97)
022 A/C Input 4 Enter: "00" No Assignment (N/A) 022
Terminals 103 & 105 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*
Note: Or can be used for Master Reset.
Note: For "Remote Start" operation either this code or code 028 must be programmed "11" (Permissive 1 Contact), code 807 must be
programmed "5" ("Remote Start") and jumpers must be installed as shown in the Installation Manual (MN06064).
023 A/C Input 5 Enter: "00" No Assignment (N/A) 023
Terminals 104 & 105 "01" Additive Feedback 1 (AFB1)
"02" Additive Feedback 2 (AFB2)
"03" Additive Feedback 3 (AFB3)
"04" Additive Feedback 4 (AFB4)
"05" Additive Feedback 5 (AFB5)
"06" Additive Feedback 6 (AFB6)
"07" Additive Feedback 7 (AFB7)
"08" Additive Feedback 8 (AFB8)
"09" First/Second High Flow (FSC)
"10" Printer Tray Switch (PTS)*
"11" Permissive 1 Contact (PRC1)
"12" Permissive 2 Contact (PRC2)
"13" Valve Power (VPW)
"14" Valve Stem-Product 1 (VST1)
"15" Valve Stem-Product 2 (VST2)
"16" Valve Stem-Product 3 (VST3)
"17" Valve Stem-Product 4 (VST4) __ __
*
Note: Or can be used for Master Reset.
Note: For "Remote Stop" operation this code must be programmed "12" (Permissive 2 Contact), code 811 must be programmed "5" ("Remote
Stop" and jumpers must be installed as shown in the Installation Manual (MN06064).