Program 
Code 
 
Function 
 
Code Description  Prod 1
 
Prod 2  Prod 3 Prod 4
 
Issue/Rev. 0.3 (8/97)  59
393  Transmitter Type  Enter:  "0" Single Channel 
      "1" Dual Channel   __  __  __  __ 
 
 
394-399  Unassigned at Present 
 
 
400  Product Temperature & Density Directory 
 
 
401-439  Unassigned at Present 
 
 
440  Protection of Program  Enter:  "0" for Weights and Measures Mode 
  Codes 480-489    "1" for Program Mode  __  __  __  __  
 
 
441  API Table & Product  Enter:  "00" No API Table     "12" API Table 24A 
      "01" API Table 5A     "13" API Table 24B  
      "02" API Table 5B     "14" API Table 24D  
      "03" API Table 5D     "15" API Table 53A  
      "04" API Table 6A     "16" API Table 53B  
      "05" API Table 6B     "17" API Table 53D  
      "06" API Table 6C     "18" API Table 54  
      "07" API Table 6D     "19" API Table 54A  
      "08" API Table 23A    "20" API Table 54B  
      "09" API Table 23B    "21" API Table 54C  
      "10" API Table 23D    "22" API Table 54D  
      "11" API Table 24  ___  ___  ___  ___  
 
 
442  Reference Density  Enter:  Five digit density 
      with floating decimal. 
      (e.g., 0999.9 to 0.9999 
      Depending on selection in 
      code 441).  _______ _______ _______ _______  
 
 
443  Low Temperature   Enter:  Four digits. The 
  Alarm    first digit indicates polarity. 
      First digit "0" = Positive 
      First digit "1" = Negative 
      The last three digits 
      indicate temperature in whole 
      degrees. (e.g., 0020 = + 020) 
      Temperature units are dependent 
      on entry made in code 441 
      An entry of -999 will disable 
      this feature.  _____ _____ _____ _____