Program
Code
Function
Code Description Prod 1
Prod 2 Prod 3 Prod 4
58 Issue/Rev. 03 (8/97)
354 Dual Pulse Error Enter: Three digits indicating
Count the number of error counts
from the dual pulse Comparator
prior to alarming. (e.g., 050) ______ ______ ______ ______
Note: "000" disables the error counting.
355 Dual Pulse Error Enter: "0" No DPC Error Reset
Reset "1" Reset at the End of Transaction Only
"2" Reset Upon Power-up Only
"3" Reset Upon Power-up and
at the End of Each Transaction __ __ __ __
356 Dual Pulse Flow Enter: Three digits defining
Rate Cutoff the flow rate that the
Dual Pulse errors will begin
to be counted. _ _ _ _ _ _ _ _ _ _ _ _
357-389 Unassigned at Present
390 Master Meter Factor Enter: Five digits as one
whole number followed by
four decimals (e.g., 1.0040)
Restricts meter factors 1
through 4, program codes 353, 355,
357, and 359 to +/- 2% of this
entry. Enter 0.0000 to disable
this feature. _._____ _._____ _._____ _._____
391 Linearized Factor Enter: Three digits in
Deviation a percentage, one whole number
followed by two decimals
(e.g., 3.40). Restricts deviation
between adjacent meter
factors. Enter 0.00 to disable
this feature. _.___ _.___ _.___ _.___
392 Meter Factor Variation Enter: "0" No Meter Factor Variation
"1" Yes Meter Factor Variation __ __ __ __