MN F08 003 US / DOK-450E Rev. 1.03 / JS / jp / March 2010 13
3 Commissioning
The EPE2-Controller is factory set so that no adjustments are required rafter installation. Just the
operating mode, switching logic and the sensor type have to be checked and adapted if necessary.
3.1 Adaptation of the operating mode
A difference is made between the “Stand-Alone residue discharge“ and “MultiFlow residue
discharge“.
Both operating modes as well as other settings are made via the DIP switch S1 on the REC-1S
printed circuit board (see also Figure 6 / page 18).
The DIP switch S1 settings are shown in the following table.
DIP switch S1
on the REC-1S board
MultiFlow residue discharge
(from MID version 5.00)
1 = ON With MultiFlow
2 = OFF No Test
3 = ON Only channel 2
4 = OFF Reserved
5 = ON |
6 = OFF | CAN-Bus
7 = ON | address = 5
8 = OFF |
DIP
switch S1
on the REC-1S board
Stand-Alone
1 = OFF Stand-Alone
2 = OFF No Tes t
3 = ON Only channel 2
4 = OFF Reserved
5 = x |
6 = x | CAN-Bus
7 = x | address = xx
8 = x |
Table 1: DIP switch S1 settings