To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button
:
To move to the next horizontal parameter press the button
:
Max Lev-press
XX.XX
Start Level P2
XX.XX
Filter reading
Coeff. K= XXX
Max Lev-press
XX.XX
The parameter “Max Lev-Press” (Alarm for max level or pressure) will set the level (in bar or
meter units depending on the mode previously selected) for which to trigger the alarm (high
level). At the activation of the level’s alarm, it is possible to start all pumps by setting the
parameter “Enable Max 4-20mA” (please refer to the section “Enable Max 4-20mA”). In addition
to the displayed alarm, depending on the settings of the associated menu, it is possible to
activate one or more output relays. In case of pressurized systems this alarm corresponds to
the pressure parameter “alarm level of pressure”.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Filter reading
Coeff. K: XXX
Max Lev-press
XX.XX
0=bar 1=mt
Value X
The parameter “Stop Level P1” will set the level (in bar or meter units depending on the mode
previously selected) for which to stop Pump 1. In the case of a pressurized system this alarm
corresponds to the pressure parameter “Pressure stop P1”.
This parameter is usable only in the DIGIT programming mode and in the MULTITANK
programming mode (only for Pump 1). In all other programming modes this parameter is
inhibited.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Start Level P2
XX.XX
Stop Level P1
XX.XX
Stop Level P2
XX.XX
Similarly to the previous parameter, the parameter “Stop Level P2” will set the level (in bar or
meter units depending on the mode previously selected) for which to stop the Pump 2. In the
case of a pressurized system this alarm corresponds to the pressure parameter “Pressure stop
P2”.
This parameter is usable only in the DIGIT programming mode. In all other programming
modes this parameter is inhibited.
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Stop Level P1
XX.XX
Stop Level P2
XX.XX
Start Level P2
XX.XX
Similarly to the previous parameter, the parameter “Start Level P2” will set the level (in bar or
meter units depending on the mode previously selected) for which to start the Pump 2. In the
case of a pressurized system this alarm corresponds to the pressure parameter “Pressure start
P2”.
This parameter is usable only in the DIGIT programming mode. In all other programming
modes this parameter is inhibited.
(The “X” indicates the digit of the parameter to modify).
The range of value is from 00.00 to 99.99.
Factory default setting: 00.00.
Stop Level P2
XX.XX
Start Level P2
XX.XX
Max Lev-press
XX.XX