25
To move to the next horizontal parameter press the button
:
Press the button
to move to the menu for setting the maximum number of starts per hour (“Max Starts per Hour”):
To continue programming the parameters of the pump press the button
to go back to the parameter “Enable Max
Start Hour”:
To move to the next horizontal parameter press the button
:
Enable Max Start
Hour 0=NO X
Enable Max Start
Minute 0=NO X
Enable Max Int.
Klixon 0=NO X
Enable Max Start
Hour 0=NO X
The parameter “Enable Max Start Hour” will enable/disable the alarm for the maximum number
of starts per hour of the pump. When enabled and the pump executes a number of starts per
minute higher than the set value “Max Starts per Hour” the alarm will activate and the pump
will stop. The functional operation of the pump will be inhibited until the reset of the alarm. The
reset of the alarm will happen automatically at the end of the Hour.
The “X” indicates the setting of the parameter to modify.
0=NO: setting “0” will disable the alarm for max number of starts per hour of the pump.
1=YES: setting “1” will enable the alarm for max number of starts per hour of the pump.
Factory default setting: 0 (disable).
The parameter “Max Starts per Hour” will set the pump’s maximum number of starts per hour.
If the pump executes a number of starts per hour higher than the set value it will be stopped
and an alarm will activate. The functional operation of the pump will be inhibited until the reset
of the alarm. The reset of the alarm will happen automatically at the end of the hour.
The “X” indicates the setting of the parameter to modify.
The range of value is from 1 to 99.
Factory default setting: 6.
Enable Max Start
Hour 0=NO X
Enable Max Start
Minute 0=NO X
Enable Max Int.
Klixon 0=NO X
Max Starts
per Hour XX
Enable Max Int.
Klixon
0=NO X
Enable Max Start
Hour
0=NO X
Enable Service
Request 0=NO X
Enable Max Int.
Klixon 0=NO X
The parameter “Enable Max Interventions Klixon” will enable/disable the alarm for the
maximum number of Klixon events for the pump. When enabled and the number of Klixon
events on the pump is higher than the set value in the parameter “Max Intervention Klixon” the
alarm will be activated and the pump will stop. The functional operation of the pump will be
inhibited until the reset of the alarm. The Klixon is a thermal protection circuit breaker
(available only on some types of pumps) inserted in the motor to prevent overheating (typically
due to an excessive number of starts within a short period of time or due to a defective cooling
system of the motor). Typically it is a bimetallic circuit breaker that provides a contact normally
closed that would open in case of overheating. The re-closing of the contact (and reactivation of
Klixon) is automatic once the temperature has dropped, below the value determined not to be
harmful to the system.
The “X” indicates the setting of the parameter to modify.
0=NO: setting “0” will disable the alarm for the maximum number of Klixon events
1=YES: setting “1” will enable the alarm for the maximum number of Klixon events
Factory default setting: 0 (disable).
Enable Max Start
Hour 0=NO X
Max Starts
per Hour XX