TROUBLE SHOOTING
FAULT
POSSIBLE CAUSE
REMEDY
Heated section does not
operate
The mains switch is off, circuit
breaker or fuses are off at the
power board
Turn mains switch on and
check circuit breakers and
fuses
Heated section temperature
incorrect
Heating element failed
Check and replace
Incorrect thermostat setting
Adjust (CW to increase temp)
Strong draught
Relocate or shield cabinet
Refrigerated section does not
operate/start
The mains isolating switch on
the wall, circuit breaker or
fuses are off at the power
board
Turn isolating switch circuit
breaker or fuses on
High condenser temperature
Clean condenser radiator
Refrigerated section is not cold
enough
Ventilation grills are blocked
Vacuum or remove blockage
Product blocking air grill
Place product on shelves
Evaporator coil fins blocked
Clean coil fins of debris etc.
Strong draught
Relocate or shield cabinet
Trays obstructing air flow
Re-position trays on shelves
Thermostat needs adjustment
Adjust the controller
Ambient temperature > 25C
Adjust store air conditioning
Evaporator coil iced up
De-ice coil
Condenser radiator blocked
Remove dust and debris
Thermostat faulty
Replace the controller
Temperature probe damaged
Replace temperature probe
Defrost cycle not suitable
Adjust to match
environment
Fans not operating
Have fans checked/replaced
Cabinet lights not working
LED strip has failed
Replace LED strip
Internal circuit breaker has
tripped
Have wiring checked and
reset circuit breaker
Water on floor
Boil off element failed
Have element replaced
Float switch faulty
Have switch replaced
Float switch relay faulty
Have relay replaced
High humidity atmosphere
Temporary condition, no
remedy
Refrigerated section circulation
fan rattling
Build-up of ice in cabinet well
due to blocked drain or cabinet
not being level
Clear drain, level cabinet and
defrost ice
Service
Personnel Only
The table entries in italics indicate actions to be taken only by qualified Service
Personnel.