Dixell XR40CX Alarm Responses
COMBINED FOOD & BEVERAGE CABINETS
-
TROUBLE SHOOTING
P1, P2, P3 or P4 Alarm – Probe fault:
Check appropriate probe wiring and probe resistance. Repair or replace as
required.
HA Alarm – High cabinet internal temperature alarm:
Clean condenser and condenser pre filter if fitted. Check evaporator coil for ice
build-up and defrost as required. Check for correct air circulation. Check
refrigeration system for correct operation.
HA2 Alarm – High discharge pipe temperature alarm:
Clean condenser and condenser pre filter if fitted. Check condenser fan for
correct operation. Check gas pressures, system may be over charged or low on
refrigerant.