12 | Technical data
Power Quality Controller – PQC | Operating Manual | FRAKO
USB for updates
(service interface)
USB Micro A and Micro B ports
Type xxxxxxx-x1
Digital inputs and
outputs
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 70 °C
Temperature
inputs
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 70 °C
Type xxxxxxx-2x
Modbus RTU
interface
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 70 °C
Type xxxxxxx-3x
Ethernet interface Ethernet cable Cat 5 as per TIA-568A/B, S/FTP shielding, RJ45 plug
Type xxxxxxx-4x
FRAKO
Starkstrombus
(Frakobus)
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 70 °C
Input for prole
switching
Conductor cross section max. 1.5 mm², min. 0.14 mm²
Insulation rating: 50 V DC, 70 °C
Note
0.14 mm
2
= AWG 26; 0.2 mm
2
≈ AWG 25;
1.4 mm² ≈ AWG 16; 2.5 mm² = AWG 14
Design data:
Dimensions
(W x H x D)
144 mm × 144 mm × 70 mm casing
144 mm × 165 mm × 70 mm casing including connectors
Mounting
Front of panel in 138 mm x 138 mm cutout to IEC 61554,
held by four retaining lugs at the corners of the casing
Maximum screw tightening torque 0.4 Nm
Weight approx. 770 g without packaging
Ingress protection
Front of instrument when mounted in cabinet IP40, when mounted in
cabinet with upgrade kit (Article No. 20-50015) IP54; rear of instrument
and terminals IP20; all as per EN 60529
Pollution degree 2 as per EN 61010-1:2011-07.