What to do if frako PQC shows 'Connection not detected' or 'Stages not detected'?
- JJessica AcevedoNov 21, 2025
Several issues can cause this problem. First, a fault in the control circuit or missing/defective fuses for the capacitor stages could be the reason. Check the control circuit against the connection diagram and verify the fuses. Ensure capacitors are energized after switching. The current transformer might be in the wrong location, so check its installation according to the connection diagram. Severe reactive power fluctuations can also cause this; wait for the power supply to stabilize and manually set the c/k factor and connection type. If the PQC programming has c/k, switching time delay, or discharge time set too high, check and adjust these settings. In automatic operation, an incorrectly identified response current c/k can cause the issue; check the control circuit and repeat the cal...

