OPERATING MANUAL
The controller that maximizes reliability
and monitors power quality
PQC
Power Quality Controller

Table of Contents

Questions and Answers

  • L
    Lisa MeyerSep 10, 2025
    Why frako Controller is not working?
    • L
      Lucas AshleySep 10, 2025
      If the frako Controller is not working and there is no display, it might be due to no power or the wrong voltage connected. Check that the correct instrument power supply is connected and that the fuse in the circuit has not blown.
  • D
    Deborah LarsonSep 9, 2025
    How to fix frako Controller showing no value for current?
    • W
      Wendy RamosSep 9, 2025
      If your frako Controller display shows no current value (0 A), there could be a few reasons: * There might be a break or short-circuit in the current transformer cable. Use an ammeter to check the current in the current path (I ? 0.015 A). * The current in the current path might be too low (I ? 0.015 A). Install a smaller current transformer. * The current transformer might be defective. Check the current transformer.
  • J
    Julie RasmussenAug 25, 2025
    Why is the displayed cos ? less than target on my frako PQC even with all stages switched in?
    • D
      Danny SuttonAug 25, 2025
      Several factors can cause this. The connection type might be entered incorrectly; re-select the connection type. There could be a fault in the control circuit, so check if the capacitor contactors have been activated. A fault in the capacitor circuit is also possible; check the fuses and contacts of the capacitor contactors, and measure the currents of each capacitor stage. Severe reactive power fluctuations can cause this, so read the corrective power still lacking from the menus. Lastly, a faulty calibration could be the reason; repeat the calibration procedure.
  • L
    Larry BeardSep 6, 2025
    What to do if frako Controller indicates voltage is less than set alarm limit?
    • D
      David DanielSep 6, 2025
      If the frako Controller indicates that the voltage is less than the set alarm limit, even though a voltage is displayed, it's likely that the alarm limit hasn't been adjusted for the network nominal voltage. To fix this, set the correct alarm limit for the network nominal voltage.
  • M
    Ms. Diana JarvisSep 5, 2025
    What to do if frako Controller shows no measured voltage and current?
    • E
      Emily PopeSep 5, 2025
      If your frako Controller shows no measured voltage and no current, and you've verified the power and current are connected, it may be due to multiple zero-voltage crossings in the measured voltage. To resolve this, go to the Network nominal parameters settings and change the setting from Auto to the appropriate network frequency (50 Hz or 60 Hz).
  • P
    Patrick MeyerSep 4, 2025
    What to do if frako PQC Controller shows 'Voltage less than set limit'?
    • L
      Lisa MillerSep 4, 2025
      Set the correct alarm limit for the network nominal voltage, because the alarm limit has not been adjusted for the network nominal voltage. Note that the default setting is for 400 V networks and is triggered when the network voltage is less than 85 % of the nominal voltage.
  • C
    Christopher BergSep 2, 2025
    What to do if frako PQC Controller displays 'Switching cycles greater than set limit'?
    • A
      April ParkSep 2, 2025
      Replace the contactors concerned and clear their switching cycle counters.
  • J
    John PowellSep 1, 2025
    Why are capacitor contactors not activated on my frako Controller?
    • R
      rebecca36Sep 1, 2025
      This problem means that the control circuit is not connected properly or there is no control voltage. Check the control circuit against the connection diagram and check the fuse of your frako Controller.
  • J
    John LynnAug 31, 2025
    Why does the LCD backlighting on my frako Controller flicker and restart?
    • M
      Mary WatsonAug 31, 2025
      The issue is likely due to the instrument power supply voltage being too low. Check whether the correct voltage is reaching the frako Controller. Also, check for high contact resistance in the power supply circuit.
  • W
    Walter WalkerAug 30, 2025
    What does 'Zero stage detected' mean on my frako Controller?
    • R
      Ryan HardyAug 30, 2025
      This error on the frako Controller may occur if capacitor stage(s) has/have lost capacitance, in this case, replace the capacitors. It can also be caused by an unstable network, where the PQC mistakenly detects a loss of capacitance, in this case, deactivate the zero stage detection function.

Summary

About This Manual

Manual Objective and Safekeeping

Purpose of the manual and instructions for its storage.

Symbols and Warning Signs

Explanation of symbols and warning sign conventions used throughout the manual.

Reference Documents

Lists related documentation for further information on the PQC.

Safety

Intended Use and Potential Dangers

Defines the proper application of the PQC and lists instrument-specific hazards.

Management Information and Disclaimer

Outlines personnel qualifications, user responsibilities, and liability limitations.

Relevant Standards and Repair

Lists applicable standards for installation and procedures for obtaining repair services.

Technical Data

Instrument Description

Function and Operation

Explains the PQC's function, power factor correction, and regeneration modes.

Instrument Versions and User Interface

Details PQC models and describes the device's operating keys and their functions.

Password Protection

Explains the system for securing sensitive menu items from unauthorized access.

Installation

Mounting and Location Procedures

Covers preparation, suitable location selection, and physical mounting of the PQC.

Electrical Installation and Connections

Details electrical wiring, specifications, diagrams, and connection steps for the PQC.

Commissioning and Initial Start-up

Covers start-up preparations, initial setup dialogue, and connection/stage identification.

Description of the Menu

Main Menu Overview

Introduces the main menu structure and primary groups: Display, Configuration, About PQC.

Display Options

Details available displays for PFC overview, System & PQ, Service, and Alarms.

Configuration Options

Explains parameter settings for system, PFC equipment, control, alarms, and communication.

Service Functions and Interface

Covers temperature I/O, communication, service interface, and 'About PQC' information.

General Operation

Cleaning and Maintenance

Safety, Cleaning, and Maintenance

Provides safety warnings, cleaning methods, and maintenance information for the PQC.

Troubleshooting

Alarm and Fault Resolution Guide

A guide for identifying and resolving common PQC alarms and faults.

Decommissioning and Disposal

Decommissioning and Removal Procedures

Details procedures for safely decommissioning and removing the PQC from installation.

Storage and Disposal Guidelines

Provides instructions for storing the PQC and guidelines for environmentally sound disposal.

frako PQC Specifications

General IconGeneral
Brandfrako
ModelPQC
CategoryController
LanguageEnglish