05 - Incidental Occupancy Threshold
00-60 (05* default setting)
Select the minimum period of time (in minutes) for which occupancy needs to be
detected to enter the occupant occupancy mode.
When occupancy is detected, Wall Controller will switch to occupied mode for a
duration of “Incidental Occupancy Threshold” selected here.
If occupancy is detected for a period of time shorter than the “Incidental
Occupancy Threshold” selected here, the Wall Controller will automatically revert
to unoccupied mode at the end of the “Incidental Occupancy Threshold” period
and continue to observe energy saving functions that were in e ect before the
room became occupied.
This setting allows ignoring incidental room visits. If occupancy is detected for
a period of time longer than the “Incidental Occupancy Threshold” selected
here, the Wall Controller will enter occupied mode. When the Wall Controller
is in occupied mode, it will revert to unoccupied mode and initiate the setback
temperature only when occupancy is not detected for the duration of the setback
delay (Heat or Cool) period.