37
14 – Temperature Setback Delay- Cool
00-120 (20* default setting)
Select the time delay (in minutes) for which the room that is in the occupant
occupancy mode needs to be unoccupied before the temperature setback is
initiated.
This feature prevents initiating temperature setback prematurely while the
occupant is still in the room but in an area where occupancy cannot be detected
by the occupancy sensor.
Setting the “Temperature Setback Delay - Cool” to “00”, disables the setback in
the cool mode. Set to “00” to disable EMS.
Custom Energy Savings Settings