EasyManua.ls Logo

Friedrich VRPXEMRT2 - Temperature Setback Delay - Heat

Friedrich VRPXEMRT2
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
12– Temperature Setback Delay - Heat
00-120 (20* default setting)
Select the time delay (in minutes) for which the room that is in the occupant
occupancy mode needs to be unoccupied before the temperature setback is
initiated.
This feature prevents initiating temperature setback prematurely while the
occupant is still in the room but in an area where occupancy cannot be detected
by the occupancy sensor.
Setting the “Temperature Setback Delay - Heat” to “00”, disables the setback in
the heat mode. Set to “00” to disable EMS.
Custom Energy Savings Settings

Related product manuals