43
20 – Auto Changeover Set Point Offset
00-04 (01°F* default setting)
Select the di󰀨 erence between the occupant-selected set point and the heat and
the cool set point when the Wall Controller is in the automatic temperature control
mode.
This value plus the 1st stage di󰀨 erential de ned in steps 02 and 04, de nes the
temperature at which the Wall Controller would automatically change heating/
cooling modes.
This feature allows adjusting the deadband between the heat and the cool set
points in automatic changeover mode in order to avoid the system from bouncing
back and forth between heating and cooling under normal operating conditions.