36
13 – Minimum Setback Temperature
52-72 (64°F* default setting)
Select the “Minimum Setback Temperature” in °F. Setback temperature is
calculated by measuring VRP unit’s ability to attain “Recovery Temperature -
Heat” within “Temperature Recovery Time”.
If recovery is disabled (“Temperature Recovery Time” is set to “0”) or if setback
temperatures have not yet been calculated, the “Minimum Setback Temperature”
value will be used as the setback temperature for heating.
If calculated setback temperature for heating is lower than “Minimum Setback
Temperature”, then the “Minimum Setback Temperature” will be used as setback
temperature for heating.
This feature allows de ning the minimum temperature in a room when room is
unoccupied and the Wall Controller is in the setback mode.