5 | Assembly
30 M2320121_en | Installation instructions Pellet boiler PECO
5.6 Setting up in the boiler room
5.6.1 Moving the boiler in the boiler room
r Position a forklift or similar lifting device with a suitable load-bearing capacity at the
base frame
r Lift and transport to the intended position in the installation room.
Ä Pay attention to the operating and maintenance areas of the equipment in the
process!
5.6.2 Operating and maintenance areas of the equipment
The system should generally be set up so that it is accessible from all sides allowing
quick and easy maintenance.
Regional regulations regarding necessary maintenance areas for inspecting the
chimney should be observed in addition to the specified distances!
Observe the applicable standards and regulations when setting up the system.
Observe additional standards for noise protection!
(ÖNORM H 5190 - Noise protection measures)
Operating and maintenance areas
B
D
A
E
C
15-20 25-35
A 600 mm
B 300 mm
C 300 mm
C1 250 mm
C2 750 mm 790 mm
D 100mm
E 500 mm
1)
1. Maintenance area to expand the WOS springs upwards