Installation
Transport and setup
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestrasse 12, A-4710 Grieskirchen Page 15
Tel +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 info@froeling.com www.froeling.com
M1010108_en
3
3.2.3 Minimum distances in the boiler room
The boiler should always be set up so that it is fully accessible to
allow fast and easy maintenance.
Observe the applicable standards and regulations when setting up
the boiler.
Also observe the standards pertaining to noise protection
(ÖNORM H 5190 - Noise protection measures)
Dimension Description Units 28 - 55
A Minimum distance from back of boiler to
wall
500
B Minimum distance from front of boiler to
wall (space required for opening insulating
door)
800
C Minimum distance between stoker and
wall
300
D Minimum distance from edge of boiler to
wall (space required to empty ashcan)
mm
700
3.2.4 General information for boiler room
Danger of fire due to flammable materials.
No flammable materials should be stored near the boiler.
Damage due to impurities in combustion air.
Do not use any solvents or cleaning agents containing chlorine in the
room where the boiler is installed.
Keep the air suction opening of the boiler free of dust.
The room where the boiler is installed must be frost-proof.