- Short clearing time for a deviation from the outer limit
- Longer clearing time for a deviation from the inner limit
U IL Max
Upper inner grid voltage limit in V
U IL/TRIP Max
Clearing time for exceeding the upper inner grid voltage limit in P**
U IL Min
Lower inner grid voltage limit in V
U IL/TRIP Min
Clearing time for falling below the lower inner grid voltage limit in P**
U OL Max
Upper outer grid voltage limit in V
U OL/TRIP Max
Clearing time for exceeding the upper outer grid voltage limit in P**
U OL Min
Lower outer grid voltage limit in V
U OL/TRIP Min
Clearing time for falling below the lower outer grid voltage limit in P**
U RC Max
"Reconnection"
Upper voltage limit for reconnecting to the public grid after disconnection due to an unac-
ceptable parameter deviation
U RC Min
"Reconnection"
Lower voltage limit for reconnecting to the public grid after disconnection due to an unac-
ceptable parameter deviation
U LL
"Longtime Limit"
Voltage limit in V for the voltage average determined over a longer time period
FREQ IL Max
Upper inner grid frequency limit in Hz
FREQ IL/TRIP Max
Clearing time for exceeding the upper inner grid frequency limit in P**
FREQ IL Min
Lower inner grid frequency limit in Hz
FREQ IL/TRIP Min
Clearing time for falling below the lower inner grid frequency limit in P**
FREQ OL Max
Upper outer grid frequency limit in Hz
FREQ OL/TRIP Max
Clearing time for exceeding the upper outer grid frequency limit in P**
FREQ OL Min
Lower outer grid frequency limit in Hz