General data
Protection class IP 66
Dimensions H x W x D 530 × 474 × 165 mm
Weight 17 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C – +60 °C
Permissible humidity 0 – 100% (incl. condensation)
EMC emission class
(according to IEC 61000‑6‑2,
IEC 61000‑6‑3)
B
DC/AC overvoltage category
(according to IEC 62109-1)
2 / 3
Pollution degree 2
Sound pressure 42 dB(A) (ref. 20µPa)
Safety class (according to IEC 62103) 1
Protection devices
DC isolation measurement
11)
Warning / shutdown at R
ISO
<
100 kOhm
Overload performance Operating point shift, power limitation
DC disconnector Integrated
RCMU
11)
Integrated
RCMU classification The software class of the safety plat-
form(s) is specified as a class B con-
trol function (single channel with peri-
odic self-test) according to IEC 60730
Annex H.
Active anti-islanding method Frequency conversion method
AFCI Integrated
AFPE (AFCI) classification (according
to IEC63027)
11)
= F-I-AFPE-1-4-1
Full coverage
Integrated
AFPE
1 monitored string per input port
4 input ports per channel (MPP1: 2,
MPP2: 2)
1 monitored channel
Data communication
WLAN SMA-RP connection
(FCC ID: QKWPILOT01 / IC ID:
12270A-PILOT01)
802.11b/g/n (WPA, WPA2)
Frequency: 2.4 GHz
Ethernet (LAN) RJ45, 10/100 MBit
Wired shutdown (WSD) Max. 28 devices / WSD chain
Max. distance between two devices =
100 m
Modbus RTU SunSpec (2x) RS485 2-wire
199