Fronius Symo Fronius Eco
Maximum fuse
rating on altern-
ating current
side
Inverter Phases AC output
Maximum output overcur-
rent protection
Fronius Symo 10.0-3-M 3 10,000 W C 80 A
Fronius Symo 12.0-3-M 3 12,000 W C 80 A
Fronius Symo 12.5-3-M 3 12,500 W C 80 A
Fronius Symo 15.0-3-M 3 15,000 W C 80 A
Fronius Symo 17.5-3-M 3 17,500 W C 80 A
Fronius Symo 20.0-3-M 3 20,000 W C 80 A
Fronius Eco 25.0-3-M 3 25,000 W C 80 A
Fronius Eco 27.0-3-M 3 27,000 W C 80 A
Note!
Local regulations, the electricity retailer or other factors may require a residual-
current protective device in the AC connection lead.
A type A residual-current circuit breaker with a trip current of at least 100 mA is
generally sufficient in this case. In particular cases, and depending on local
factors, however, the type A residual-current circuit breaker may trip at the
18

Table of Contents

Other manuals for Fronius Symo 15.0-3-M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius Symo 15.0-3-M and is the answer not in the manual?

Fronius Symo 15.0-3-M Specifications

General IconGeneral
Max. efficiency98.1%
Max. input voltage1000 V
MPPT voltage range200 - 800 V
Weight34.8 kg
Protection ratingIP 66
Max. output current21.7 A
AC nominal voltage400 V
AC voltage range320 - 480 V
Frequency50 / 60 Hz
THD< 3%
Number of MPP trackers2
AC Frequency Range50 / 60 Hz
Maximum Efficiency98.1%
Warranty5 years
AC nominal output15000 W
Max. apparent AC power15 kVA
Maximum AC Power15000 VA
Maximum DC Power22500 W
Operating Temperature Range-25 to +60 °C
Max. input current30 A
Max. input current (Idc max)30 A
CoolingForced air cooling