5-61
H06 Cooling Fan ON/OFF Control
To prolong the life of the cooling fan and reduce fan noise during running, the cooling fan stops
when the temperature inside the inverter drops below a certain level while the inverter stops.
However, since frequent switching of the cooling fan shortens its life, the cooling fan is kept
running for 10 minutes once it is started.
H06 specifies whether to keep running the cooling fan all the time or to control its ON/OFF.
Data for H06
Cooling fan ON/OFF
0
Disable (Always in operation)
1
Enable (ON/OFF controllable)
H07 Acceleration/Deceleration Pattern
H07 specifies the acceleration and deceleration patterns (patterns to control output
frequency).
Linear acceleration/deceleration
The inverter runs the motor with the constant acceleration and deceleration.
S-curve acceleration/deceleration
To reduce an impact that acceleration/deceleration would make on the machine, the inverter
gradually accelerates/decelerates the motor in both the acceleration/deceleration starting and
ending zones. Two types of S-curve acceleration/deceleration are available; 5% (weak) and
10% (strong) of the maximum frequency, which are shared by the four inflection points. The
acceleration/deceleration time command determines the duration of
acceleration/deceleration in the linear period; hence, the actual acceleration/deceleration
time is longer than the reference acceleration/deceleration time.