5-2
(F codes continued)
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
F26 0.75 to 15 1 kHz Y Y 2 5-34
F27 (Tone) 0: Level 0 (Inactive)
㧙㧙
YY 0
1: Level 1
2: Level 2
3: Level 3
F29 Analog Output [FM] 0: Output in voltage (0 to 10 VDC) (
FMA
)
㧙㧙
YY 05-35
(Mode selection) 2:
Out
F30 (Voltage adjustment) 0 to 300 (
FMA
)1%Y*Y100
F31
㧙㧙
YY 0
0: Output frequency 1 (before slip compensation)
1: Output frequency 2 (after slip compensation)
2: Output current
3: Output voltage
4: Output torque
5: Load factor
6: Input power
7: PID feedback amount (PV)
8: PG feedback value
9: DC link bus voltage
10: Universal AO
13: Motor output
14: Calibration
15: PID command
16: PID output (MV)
F33 (Pulse rate) 25 to 6000 (
FMP
, Pulse rate at 100% output) 1 p/s Y* Y 1440
F37 0: Variable torque load
㧙㧙
NY 15-23
1: Constant torque load
2: Auto-torque boost
3:
4:
5:
F39 Stop Frequency 0.00 to 10.00 0.01 s Y Y 0.00 5-34
(Holding Time)
F40 1% Y Y 999 5-36
F41 1% Y Y 999
F42 Control Mode Selection 1 0:
㧙㧙
NY 05-37
1: Dynamic torque vector control
2:
3:
4:
F43 Current Limiter 0: Disable (No current limiter works.)
㧙㧙
Y Y 2 (Note) 5-38
(Mode selection) 1:
2: Enable during ACC/constant speed operation
F44 (Level) 1 % Y Y 180 (Note)
F50 1 to 900 1kWs Y Y 999
999: Disable
(Discharging capability) 0: Reserved
F51 (Allowable average loss) 0.001 kW Y Y 0.000
Motor Sound
ޓ
(Carrier frequency)
Name
Enable at constant speed (Disable during ACC/DEC)
20 to 200 (The data is interpreted as the rated output current of the inverter
for 100%.
V/f control with slip compensation inactive
V/f control with slip compensation active
20 to 200
999: Disable
Auto-energy saving operation (Auto-torque boost during ACC/DEC)
Dynamic torque vector control with optional PG interface
Select a function to be monitored from the followings.
Auto-energy saving operation (Variable torque load during ACC/DEC)
Auto-energy saving operation (Constant torque load during ACC/DEC)
V/f control with optional PG interface
20 to 200
999: Disable
0.001 to 50.000
0.000: Reserved
Data setting range
Load Selection/Auto Torque Boost/
Auto Energy Saving Operation 1
Electronic Thermal Overload Protection
for Brakin
Resistor
Torque Limiter 1
(Limiting level for driving)
(Limiting level for braking)
The shaded function codes ( ) are applicable to the quick setup.
(Note) Default settings for inverters with inverter's ROM version 0799 or earlier: F43 = 0 and F44 = 200 (For the inverter's ROM
version checking procedure, refer to Chapter 3, Section 3.4.6 "Reading maintenance information".)