Loading...
5-5
(E codes continued)
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
E40 PID Displa
y
Coefficient A -999 to 0.00 to 9990 *1 0.01
YY 100 -
E41 PID Display Coefficient B -999 to 0.00 to 9990 *1 0.01
Y Y 0.00
E42 LED Display Filter 0.0 to 5.0 0.1 s Y Y 0.5
E43 0: Speed monitor (select by E48)
㧙㧙
YY 0
3: Output current
4: Output voltage
8: Calculated torque
9: Input power
10: PID command
12: PID feedback amount
13: Timer
14: PID output
15: Load factor
16: Motor output
21: Current position pulse count *5
22: Position deviation pulse count *5
E45 0:
㧙㧙
YY 0
1:
E46 (Language selection) 0: Japanese
㧙㧙
YY 1
1: English
2: German
3: French
4: Spanish
5: Italian
E47 (Contrast control) 0 (Low) to 10 (High) 1
YY 5
E48 LED Monitor (Speed monitor item) 0: Output frequency (Before slip compensation)
㧙㧙
YY 0
1: Output frequency (After slip compensation)
2: Reference frequency
3: Motor speed in r/min
4: Load shaft speed in r/min
5: Line speed in m/min
6: Constant feedin
g
rate time
E50 0.01 to 200.00 *1 0.01
Y Y 30.00
E51 0.001
Y Y 0.010
E52 Keypad (Menu display mode) 0: Function code data editing mode (Menus #0 and #1)
㧙㧙
YY 0 -
1: Function code data check mode (Menu #2)
2: Full-menu mode (Menus #0 through #6)
E59 0: Current input
(
C1 function
)
, 4 to 20 mADC
㧙㧙
NY 05-53
1: Voltage input (V2 function), 0 to +10 VDC
E61
㧙㧙
NY 05-54
E62 0: None
㧙㧙
NY 0
(C1 function) 1: Auxiliary frequency command 1
E63 2:
A
uxiliar
y
frequenc
y
command 2
㧙㧙
NY 0
(V2 function) 3: PID command 1
5: PID feedback amount
E65 1% Y Y 9990: Decelerate to stop
20 to 120
999: Disable
5-53
0.000 (Cancel/reset
0.001 to 9999
Bar charts for output frequency, current and calculated torque
Running status, rotational direction and operation guide
Reference Loss Detection
(Continuous running frequency)
Terminal [C1] Extended Function
Terminal [C1] Extended Function
Coefficient for Speed Indication
Terminal [12] Extended Function
LCD Monitor *3 (Item selection)
Display Coefficient for Input Watt-hour
Data
LED Monitor (Item selection)
Terminal [C1] Signal Definition
(C1/V2 Function)
Selecting function code data assigns the corresponding function to
terminals [12] and [C1] (C1/V2 function) as listed below.
Name Data setting range
The shaded function codes ( ) are applicable to the quick setup.
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*
3
These function codes are for use with an optional multi-function keypad.
*
5
These are available on inverters with inverter's ROM version 0700 or later. (For the version checking procedure, refer to
Chapter 3, Section 3.4.6 "Reading maintenance information."
)