5-7
C codes: Control Functions
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
C01 Jump Frequenc
y
1 0.0 to 400.0 0.1 Hz Y Y 0.0 -
C02 2 YY 0.0
C03 3 YY 0.0
C04 (Hysteresis width) 0.0 to 30.0 0.1 Hz Y Y 3.0
C05 Multi-Frequency 1 0.00 to 400.00 *1 0.01 Hz Y Y 0.00
C06 2 Y Y 0.00
C07 3 Y Y 0.00
C08 4 Y Y 0.00
C09 5 Y Y 0.00
C10 6 Y Y 0.00
C11 7 Y Y 0.00
C12 8 Y Y 0.00
C13 9 Y Y 0.00
C14 10 Y Y 0.00
C15 11 Y Y 0.00
C16 12 Y Y 0.00
C17 13 Y Y 0.00
C18 14 Y Y 0.00
C19 15 Y Y 0.00
C20 Jo
gg
in
g
Frequenc
y
0.00 to 400.00 *1 0.01 Hz Y Y 0.00
C21 Timer Operation 0: Disable
㧙㧙
NY 05-55
1: Enable
C30 Frequenc
y
Command 2 0: UP/DOWN ke
y
s on ke
y
pad
㧙㧙
NY 25-18
1: Voltage input to terminal [12] (-10 to +10 VDC)
2: Current input to terminal [C1] (C1 function) (4 to 20 mA DC)
3:
5: Voltage input to terminal [C1] (V2 function) (0 to 10 VDC)
7: Terminal command
UP
/
DOWN
control
11: Digital I/O interface option
12: PG interface card (option)
C31 -5.0 to 5.0 0.1 % Y* Y 0.0 5-55
C32 (Gain) 0.00 to 200.00 *1 0.01 % Y* Y 100.0 5-32
C33 (Filter time constant) 0.00 to 5.00 0.01 s Y Y 0.05 5-55
C34 (Gain base point) 0.00 to 100.00 *1 0.01 % Y* Y 100.0 5-32
C35 (Polarity) 0: Bipolar
㧙㧙
NY 1 -
1: Unipolar
C36 -5.0 to 5.0 0.1 % Y* Y 0.0 5-55
(
C1 function
)
(
Offset
)
C37 (Gain) 0.00 to 200.00 *1 0.01 % Y* Y 100.0 5-32
C38 (Filter time constant) 0.00 to 5.00 0.01 s Y Y 0.05 5-55
C39
(
Gain base
p
oint
)
0.00 to 100.00 *1 0.01 % Y* Y 100.0 5-32
C41 -5.0 to 5.0 0.1 % Y* Y 0.0 5-55
(
V2 function
)
(
Offset
)
C42
(
Gain
)
0.00 to 200.00 *1 0.01 % Y* Y 100.0 5-32
C43
(
Filter time constant
)
0.00 to 5.00 0.01 s Y Y 0.05 5-55
C44 (Gain base point) 0.00 to 100.00 *1 0.01 % Y* Y 100.0 5-32
C50 Bias (Frequency command 1) 0.00 to 100.00 *1 0.01 % Y* Y 0.00
(
Bias base point
)
C51 Bias (PID command 1) -100.00 to 100.00 -
(Bias value) 0.01 % Y* Y 0.00
C52 (Bias base point) 0.00 to 100.00 *1 0.01 % Y* Y 0.00
C53 0: Normal operation
㧙㧙
YY 0
(Frequency command 1) 1: Inverse operation
Data setting range
Analog Input Adjustment for [12]
(Offset)
Analog Input Adjustment for [C1]
Analog Input Adjustment for [C1]
Selection of Normal/Inverse Operation
Name
Sum of voltage and current inputs to terminals [12] and [C1]
(C1 function)
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.