5-12
J codes: Application Functions
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
J01 0: Disable
㧙㧙
NY 0 -
1: Enable (Process control, normal operation)
2: Enable (Process control, inverse operation)
3: Enable (Dancer control)
J02 (Remote command SV) 0: UP/DOWN keys on keypad
㧙㧙
NY 0
1: PID command 1
3: Terminal command
UP
/
DOWN
control
4: Command via communications link
J03 P
(
Gain
)
0.000 to 30.000 *1 0.001 times Y Y 0.100
J04 I (Integral time) 0.0 to 3600.0 *1 0.1 s Y Y 0.0
J05 D (Differential time) 0.00 to 600.00 *1 0.01 s Y Y 0.00
J06
(
Feedback filter
)
0.0 to 900.0 0.1 s Y Y 0.5
J10 (Anti reset windup) 0 to 200 1% Y Y 200
J11 (Select alarm output) 0: Absolute-value alarm
㧙㧙
YY 0
1: Absolute-value alarm (with Hold)
2: Absolute-value alarm (with Latch)
3: Absolute-value alarm (with Hold and Latch)
4: Deviation alarm
5: Deviation alarm (with Hold)
6: Deviation alarm
(
with Latch
)
7: Deviation alarm (with Hold and Latch)
J12 (Upper level alarm (AH)) -100 to 100 1 % Y Y 100
J13
(
Lower level alarm
(
AL
))
-100 to 100 1 % Y Y 0
J18 (Upper limit of PID process output) 1% Y Y 999
J19 (Lower limit of PID process output) 1% Y Y 999
J56 (Speed command filter) 0.00 to 5.00 0.01 s Y Y 0.10
J57 (Dancer reference position) -100 to 100 1 % Y Y 0
J58 (Detection width of dancer 0: 1% Y Y 0
position deviation
)
1 to 100
J59 0.000 to 30.000 *1 0.001 times Y Y 0.100
J60 0.0 to 3600.0 *1 0.1 s Y Y 0.0
J61 0.00 to 600.00 *1 0.01 s Y Y 0.00
J62 (PID control block selection) 1
NY 0
J63 Overload Stop 0: Torque
㧙㧙
YY 05-73
(Detection value) 1: Current
J64 (Detection level) 20 to 200 0.1 % Y Y 100
J65 (Mode selection) 0: Disable
㧙㧙
NY 0
1: Decelerate to stop
2: Coast to a stop
3: Hit and stop
J66 (Operation condition) 0:
㧙㧙
YY 0
1: Enable at constant speed
2: Enable anytime
J67 (Timer) 0.01 s Y Y 0
J68 0 to 200 1% Y Y 100 5-74
J69 (Brake OFF frequency) 0.0 to 25.0 0.1 Hz Y Y 1.0
J70 (Brake OFF timer) 0.0 to 5.0 0.1 s Y Y 1.0
J71 (Brake ON frequency) 0.0 to 25.0 0.1 Hz Y Y 1.0
J72 (Brake ON timer) 0.0 to 5.0 0.1 s Y Y 1.0
Name
Bit 1: Select compensation of output ratio
0 =Ratio (relative to the main setting)
1 = Speed command (relative to maximum frequency)
-150 to 150
999: The F15 data applies.
-150 to 150
999: The F16 data applies.
Enable at constant speed and during deceleration
0.00 to 600.00
PID Control (Mode selection)
Braking Signal
Data setting range
(Brake OFF current)
D (Differential time) 2
Disable switching PID constant
Bit 0: PID output polarity
0 = addition, 1 = subtraction
I (Integral time) 2
P (Gain) 2
*
1
When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can
display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.