5-14
y codes: Link Functions
Code
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer to
page:
y01 RS-485 Communication (Standard) 1 to 255 -
(Station address) 1
㧙
NY 1
y02 (Communications error processing) 0: Immediately trip with alarm
GT
㧙㧙
YY 0
1:
3: Continue to run
y03 (Timer) 0.0 to 60.0 0.1 s Y Y 2.0
y04 (Baud rate) 0: 2400 bps 㧙㧙 YY 3
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y05 (Data length) 0: 8 bits
㧙㧙
YY 0
1: 7 bits
y06 (Parity check) 0: None (2 stop bits for Modbus RTU)
㧙㧙
YY 0
1: Even parity (1 stop bit for Modbus RTU)
2: Odd parity (1 stop bit for Modbus RTU)
3: None (1 stop bit for Modbus RTU)
y07 (Stop bits) 0: 2 bits
㧙㧙
YY 0
1: 1 bit
y08 (No-response error detection time) 0: No detection 1 s Y Y 0
1 to 60
y09 (Response interval) 0.00 to 1.00 0.01 s Y Y 0.01
y10 (Protocol selection) 0: Modbus RTU protocol 㧙㧙 YY 1
1: FRENIC Loader protocol (SX protocol)
2: Fuji general-purpose inverter protocol
y11 RS-485 Communication (Option) 1 to 255
(Station address) 1 㧙 NY 1
y12 (Communications error processing) 0: Immediately trip with alarm
GTR
㧙㧙
YY 0
1:
3: Continue to run
y13 (Timer) 0.0 to 60.0 0.1 s Y Y 2.0
y14 (Baud rate) 0: 2400 bps 㧙㧙 YY 3
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
y15 (Data length) 0: 8 bits
㧙㧙
YY 0
1: 7 bits
y16 (Parity check) 0: None (2 stop bits for Modbus RTU)
㧙㧙
YY 0
1: Even parity (1 stop bit for Modbus RTU)
2: Odd parity (1 stop bit for Modbus RTU)
3: None (1 stop bit for Modbus RTU)
y17 (Stop bits) 0: 2 bits
㧙㧙
YY 0
1: 1 bit
y18 (No-response error detection time) 0: No detection 1 s Y Y 0
1 to 60
y19 (Response interval) 0.00 to 1.00 0.01 s Y Y 0.01
y20 (Protocol selection) 0: Modbus RTU protocol 㧙㧙 YY 0
2: Fuji general-purpose inverter protocol
y98 Frequency command Run command
㧙㧙
YY 05-68
0: Follow H30 data Follow H30 data
1: Via field bus option Follow H30 data
2: Follow H30 data Via field bus option
3: Via field bus option Via field bus option
y99
ޓ
Frequency command Run command
㧙㧙
YN 0 -
0: Follow H30 and y98 data Follow H30 and y98 data
1: Via RS-485 link (Loader) Follow H30 and y98 data
2: Follow H30 and y98 data Via RS-485 link (Loader)
3: Via RS-485 link (Loader) Via RS-485 link (Loader)
Retry during the period specified by timer y03. If the retry fails, trip with
alarm
GT
. If it succeeds, continue to run.
Retry during the period specified by timer y13. If the retry fails, trip with
alarm
GTR
. If it succeeds, continue to run.
2:
2:
Trip with alarm
GTR
after running for the period specified by timer y13
Trip with alarm
GT
after running for the period specified by timer y03
Data setting range
Bus Link Function (Mode selection)
Loader Link Function (Mode selection)
Name