1 Installation/mounting
Outline and Panel Cutout Dimensions
63 or more
73 or more
+0.5
a
-0
Number
of units
23456
a93141 189 237 285
45
+0.5
0
45
+0.5
0
45
+0.5
0
For side by side installation,
see the Note1.
No. 000001T
PXR4TAA1-1YM00-D
MFD 2000-04
AL2AL1C1 C2 AL3
SEL
PXR-4
SV
PV
48
44.8
44.8
79.88
48
Mounting bracket
Panel
Panel thickness 1 to 8mm
Packing
48
44.8
57
6.2
Terminal screw M3×6
13
16
17
18
14
15
7
8
10
11
12
9
1
2
4
5
6
3
Outline dimensions (unit:mm)
Panel cutout dimensions
(unit:mm)
Cautions on wiring
•Wiring should be started from the left side terminal (No. 1 to No. 6).
Use crimped terminals matched to the screw size. Tightening torque should be about
0.8 N·m (Since the case is made of plastic, do not tighten excessively).
Do not connect anything to terminals not used.
Note 1
Caution on side by side installation
With the power supply of 200 VAC or more, a maximum ambient temperature is 45˚C.
(It is recommended to use a fan for cooling.)
When there is another instrument (larger than 70mm) or a wall on the right side of this controller, be
sure to install the controller keeping a space of more than 30mm.
Wateproofness cannot be ensured in the case of side-by-side installation.
30 min.
70 or more