– 27 –
The parameters “bAL and “Ar” are masked at default setting.
If necessary to appear these parameters, please refer to the following procedure.
1) Function
•“bAL and “Ar” are functions to suppress overshoot.
(Usually it is not necessary to change the setting.)
2) If they aren't optimum value, sometime you don't get the good control. Usually it is not necessary to set them.
3) “Ar”(Anti-reset wind-up) is automatically set by “Auto tuning”.
1 bAL
MV is calculated by adding the offset (bAL) to MV’, the result of PID calculation, from PV and SV.
2 Ar
The integral range is SV±Ar.
Integral action don't work when PV is out of the range.
1 To unmask
q Display the “dSP3” in the third block parameter and then subtract 128 from current value.
w Display the “dSP4” in the third block parameter and then subtract 1 from current value.
2 To mask
q Display the “dSP3” in the third block parameter and then add 128 to current value.
w Display the “dSP4” in the third block parameter and then add 1 to current value.
Mask/Unmask bAL and Ar
bAL increase
bAL decrease
bAL
50%
100%
PV
SV
PID
bAL
MV'
MV
+
+
0%
Set value (SV)
Operation value
Proportional band
Control output (MV)
MV' (PV)
Work
Time
Don't work
Integral action
Don't work
Ar
Ar
SV
PV