– 29 –
Setting of
the input type
* Skip this procedure
if the input type is
specified when
you order.
1
qPlease check if the input type set at “P-n2” is same as what
you use.
Choose the sensor type you use from Table 1 shown below, and set
the code at “P-n2”.
(Example) For T thermo-couple, set “P-n2”=7.
Please refer to the following table for the modification of the
input type.
Standard range to each sensor is shown in Table 3. Select the tem-
perature range suitable for the equipments you use, set lower/upper
limit values to “P-SL / “P-SU” respectively.
(Example) For temperature range 0 to 800 [°C] : Set “P-SL and “P-SU”
to 0 and 800 respectively.
(Note) If the span of setting ranges is smaller than the one of
minimum standard range, the accuracy (% full scale) is
influenced.
(Note) No standard range is given in case of 1 to 5VDC (4 to
20mA DC) input. Please set the range within the following
limitation.
• Maximum span : 9999
• Lower limit :
-
1999
• Upper limit : 9999
wIssetting of input temperature range suitable for the sensor
you use?
TC Can be modified by changing P-n2.RTD
(within Group I)*
TC/RTD
(Group I)*
Modification not possible
TC : Thermocouple RTD : Resistance bulb
1 to 5Vdc
4 to 20mAdc
(Group II)*
(*Please refer to table 1)
Note:
Please set
P-n2
: Input sensor type and
P-SL/P-SU/P-dP
: input range setting prior to any other parameter
settings. When
P-n2
and/or
P-SL/P-SU/P-dP
is changed, some other parameters may also be influenced.
Please check all parameters before starting control.
(Note)
7
Setting of input type and control algorithm