– 16 –
2nd block parameter
· If no operation status
continues for 30 seconds,
the screen is restored
to the PV/SV display just
after the power is turned on.
Parameter
Proportional band
Description of contents
Default
setting
Remarks
P
I
D
TC
TC2
CooL
db
P-SU
P-dP
ALM1
ALM3
HYS
Hysteresis for ON/OFF contorol
Cycle time (control output 2)
Deadband/overlap
Proportional band
coefficient on cooling side
Input type code
Lower limit of input range
As ordered
As ordered
P-n2
P-SL
As ordered
As ordered
0/5
0
5.0
Derivative action time
60.0
Integral time (reset)
240
Cycle time (control output 1)
Setting types of alarm action (Setting range: 0 to 34)
Setting of decimal point
position
PVOF
0
PV offset
Type of alarm 1
Upper limit of input range
Type of alarm 3
ALM2
0/9
Type of alarm 2
1
30/2 Note 2
30/2
1.0
0.0
PTn
1
Selects the ramp/soak execute type.
1: Executes 1st to 4th segment.
2. Executes 5th to 8th segment.
3. Executes 1st to 8th segment.
Ramp/soak execute type
SV-1
to
SV-8
0%FS
Sets the target SV for each ramp segment.
(Setting range: 0 to 100%FS)
Ramp target SV-1 to SV-8
TM1r
to
TM8r
0.00
Sets the time for each ramp segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st ramp segment time to
8th ramp segment time
TM1S
to
TM8S
0.00
Sets the time for each soak segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st soak segment time to
8th soak segmentl time
STAT
Ramp/soak status
Shift the display of process value (PV).
(Setting range: -10 to 10%FS)
Displays the current Ramp/Soak status.
No setting can be made.
Setting range: 0.0 to 999.9%
ON/OFF control when “P” = 0
Setting range: 0 to 3200 sec.
No integral action when “I” = 0
Setting range: 0.0 to 999.9 sec.
No derivative action when “d” = 0
Sets cycle time of control output 1.
(Setting range: 1 to 150 sec)
Setting range: 0 to 50% FS
Sets cycle time of control output 2.
(Setting range: 1 to 150 sec)
Sets the proportional band coefficient on the cooling side.
(Setting range : 0.0 to 100.0)
ON/OFF control when “Cool” = 0
Shifts the output value on the cooling side.
(Setting range: -50.0 to 50.0%)
Lower limit of input range
(Setting range: -1999 to 9999)
Upper limit of input range
(Setting range: -1999 to 9999)
Type of input Table 1
(Page 31)
Table 3
(Page 32)
Table 4
(Page 33)
Select a decimal point position of display.
(Setting range: 0 to 2)
. .
“1”
0 : No decimal point
“2”
CTrL
PID
Type of control algorithm.
(Setting range: PID, FUZZY, SELF)
Control algorithm
P-dF
Time constant of input filter
5.0
Time constant (Setting range: 0.0 to 900.0 sec.)
Parameter
display symbol
Note 2
Mod
Setting of ramp/soak mode
0Table 5
(Page 34)
Sets ramp/soak operation mode
Press for about 3 sec.
Operation/Standby mode
Control output status
Alarm status
PV value
indication
MV value indication lamp is lit
SV value
indication
When the set value
(SV) is displayed at
the lower line, the
SV lamp is lit.
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Manual
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Standby
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Auto
SEL
Press for about 2 sec.
SEL
Note 2) When using the heater break alarm, set the parameter “TC” to 20 or more.
Set the CT (current transformer) so that it measures the current of the heater connected
to the control output 1.
Disconnection of the control output 2 cannot be detected.
Never set “TC” / “TC2” = 0.
· Some parameters may not be displayed on the screen, depending upon the types.