– 28 –
1) Function
Outputs PV, SV, MV, and DV as a unified 4 to 20mA signal.
2) To use the Re-transmission output function,
(1) Set the output type to be outputted to Re-transmission output at .
(2) If output scaling is required, make the scaling setting at and .
Ao-T
0
1
2
3
Output type
PV
SV
MV
DV
1) Function
Controls SV (set value) by inputting 1 to 5V voltage signals by an external device.
2) To perform remote operation.
(1) Connect the remote SV voltage signal to the remote SV input terminal.
(2) If required, perform zero point or span point adjustment of remote SV input.
··· Parameter for zero point compensation of remote SV input
··· Parameter for span point compensation of remote SV input
(3) Changing parameter to switches to remote SV operation.
* is the setting for remote SV input filter. Use the equipment with the value set to 0.0 (set at the time
of delivery) unless the change is required.
1 to 5V
voltage
signal
PV
SV
6-10 Remote SV function
6-9 Re-transmission output function