– 15 –
5
Setting methods of temperature and parameters
1st block parameter
Press for about 1 sec.
Operation/Standby mode
Control output status
Alarm status
PV value
indication
MV value indication lamp is lit
SV value
indication
When the set value
(SV) is displayed at
the lower line, the
SV lamp is lit.
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Manual
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Standby
AL2AL1C1 C2 AL3
SEL
PXR
-
4
SV
PV
Auto
SEL
Press for about 2 sec.
SEL
Parameter
display symbol
Parameter
Standby settings
Description of contents
Default
setting
Remarks
STbY
ProG
LACH
AT
TM-2
AL1
A1-L
A2-L
A2-H
LoC
TM-1 Timer 1 display
Timer 2 display
Alarm 1 low limit
set value
Alarm 1 set value
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 1 high limit
set value
(appears only with alarm action type 1 to 10).
Setting range: Note 1
Alarm 2 set value
10
10
A1-H
AL2
10
10
0
Switches RUN or Standby of the control.
ON: Control standby (output: OFF, alarm: OFF)
OFF: Control RUN
Selecting manual
mode
MAnU
Switch the operation mode by selecting Auto/Manual
ON: Manual mode
OFF: Auto mode
OFF: stop, rUn: Start, HLd: status hold
0: Stop, 1: Standard AT start, 2: Low PV type AT start
OFF
Alarm latch cancel Releases alarm latch.
1: Alarm latch release
0
Ramp/soak control
CMod
Switches Local and Remote operations.
: Local operation
: Remote operation
Control mode
OFF
Auto-tuning
Time displays indicating the remining time at the timer
mode.
(appears only with alarm action type 1 to 10).
Setting range: Note 1
(appears only with alarm action type 16 to 31).
Setting range: Note 1
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 2 high limit
set value
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 2 low limit
set value
Setting of key lock status. Key lock
0
TM-3
Timer 3 display
10
Table 4
(Page 33)
Note 1
10
All parameters
Front keyLoC
0
1
2
3
4
5
Comm-
unication
SV
Front key Comm-
unication
Note 1) Setting range : 0 to 100%FS (in case of absolute value alarm)
-
100 to 100%FS (in case of deviation alarm)
· Some parameters may not be displayed on the screen, depending upon the types.
A3-L
A3-H
(appears only with alarm action type 1 to 10).
Setting range: Note 1
Alarm 3 set value
10
AL3
10
10
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 3 high limit
set value
(appears only with alarm action type 16 to 31).
Setting range: Note 1
Alarm 3 low limit
set value
: Setting enable, : Setting disable
· If no operation status
continues for 30 seconds,
the screen is restored
to the PV/SV display just
after the power is turned on.
OFF