– 32 –
Input typeGroup
I
· Pt100 (IEC)
RTD
·J
·K
·R
·B
·S
·T
·E
·N
· PL-II
1
2
3
4
5
6
7
8
12
13
Thermocouple
Code
Input typeGroup
II
1 to 5V DC,
4 to 20mA DC
16
Code
Can be modified by
changing "P-n2".
Modification not
possible.
· Modification
TC RTD
(within Group I)*
TC/RTD
1 to 5 V DC
4 to 20 mA DC
(Group I)* (Group II)*
· Input signals can be selected
within the same group.
· In case of 4 to 20mA DC input,
mount a 250Ω resistor
enclosed in the package box.
[Caution for dual output] (option)
(1) Parameter “I” and “D” can not be set separately.
(2) In case “P”=0 (ON/OFF control) for heating side, cooling side becomes ON/OFF control automatically.
(3) In case “Cool” =0.0, cooling side becomes ON/OFF control. And hysteresis is fixed at 0.5%FS.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Single
(Control output 1)
Dual
Control output
1 and 2.
Output 1
Reverse action
Direct action
Reverse action
Direct action
Reverse action
Direct action
Output 2
---
Direct action
Reverse action
Output 1
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Output 2
---
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Control output action Output at Burn-out*
Code
Output
Parameter :
[Table 2] Control output action code
(*) Outputs when Error Indication Group I.
Please refer to “8. Error indications”.
This is effective even in Standby mode.
Lower limit: OFF or 4mA or less
Upper limit: ON or 20mA or more
Parameter :
[Table 1] Input type code