– 4 –
1. Warning
1.1 Installation and wiring
• This controller designed to be installed at the following conditions.
• The controller must be installed such that with the exception of the connection to the mains, creepage
and clearance distances shown in the table below are maintained between the temperature probe
and any other assemblies which use or generate a voltage shown in the table below.
Failure to maintain these minimum distances would invalidate the EN 61010 safety approval.
• If the voltage shown above exceeds 50Vdc (i.e. hazardous voltage), the basic insulation is required
between all terminals of this controller and the ground, and supplementary insulation is required for
the alarm output.
Isolation class of this controller is as shown below. Be sure to check that the isolation class of the
controller satisfies your requirements before installation.
Operating temperature
-
10 to
+
50 [°C ]
Conforming to IEC1010-1
Installation category II
Pollution degree 2
Operating humidity 90%RH or less (Non condensation)
Up to 50Vrms or Vdc
Voltage used or generated
by any assemblies
Clearance
(mm)
Creepage
(mm)
0.2
Up to 150Vrms or Vdc 0.5
Up to 300Vrms or Vdc 1.5
Above 300Vrms or Vdc Contact with our sales office.
Up to 100Vrms or Vdc 0.2
1.2
1.6
3.0
1.4
Mains (Power source) Measured value input, CT input, Remote SV input
Control output1 (relay output) Internal circuit
Control output2 (relay output) Control output1, 2 (SSR drive output / Current output)
Alarm outout (AL1) Re-transmission
Alarm outout (AL2) Communication (RS-485) circuit
Alarm outout (AL3) or
Digital input (DI).
Heater burnout alarm output (HB)
: Basic insulation,
: Non-insulation,
: Functional insulation