8
KEYPAD PANEL
8-16
(2) Alarm reset
Resets the alarm detected by the servo amplifier.
(3) Alarm history initialization
Deletes the alarm detection log recorded in the servo amplifier. The alarm detection history (alarm
history) can be monitored in state display mode [ ].
* The alarm history is retained even when the power is turned off.
(4) Parameter initialization
Initializes the parameters.
* After initializing, turn the power off then on again.
Cause of parameter initialization failure
1. Write-protection selected at parameter #27 (write-protection of parameters)
--> Change parameter #27 (write-protection of parameters) to “0” (write-enable).
2. Active operation command [RUN]
-->Turn off the operation command [RUN].
System setting parameter #27
No. Name Setting range Initial value Change
27 Parameter write-protection 0: Write-enable, 1: Write-protection 0 Always
ENT (1 sec or more)
ESC
ENT
ESC
End of resetting
ENT (1 sec or more)
ESC
ENT
ESC
End of initialization
ENT (1 sec or more)
ESC
ENT
ESC
End of initialization Cannot be initialized