- 69 -
CASSETTE TYPE
AUXG18-54LRLB
Contents of function setting
Each function setting listed in this section is adjustable in accordance with the installation environ-
ment.
NOTE: Setting will not be changed if invalid numbers or setting values are selected.
1) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
2) Ceiling height
Select the appropriate ceiling height according to the place of installation.
For the specific height for each setting value, refer to Chapter 4. "Installation space requirement" on
page 19.
In case of cassette type models:
The ceiling height values are for the 4-way outlet. Do not change this setting in the 3-way outlet
mode.
3) Outlet directions
Select the appropriate number of outlet directions according to the installation conditions.
Function no. Functions
1)
11
Filter sign
2)
20
Ceiling height
3)
22
Outlet directions
4)
23
Vertical airflow direction range control
5)
30/31
Room temperature control for indoor unit sensor
6)
35/36
Room temperature control for wired remote controller sensor
7)
40
Auto restart
8)
42
Room temperature sensor switching
9)
44
Remote controller custom code
10)
46
External input control
11)
48
Room temperature sensor switching (Aux.)
12)
49
Indoor unit fan control for energy saving for cooling
13)
60
Switching functions for external output terminal
Function number Setting value Setting description Factory setting
11
00 Standard (2,500 hours)
01 Long interval (4,400 hours)
02 Short interval (1,250 hours)
03 No indication ♦
Function number Setting value Setting description Factory setting
20
00 Standard ♦
01 High ceiling
02 Low ceiling
Function number Setting value Setting description Factory setting
22
00 4-way ♦
01 3-way