- 70 -
CASSETTE TYPE
AUXG18-54LRLB
4) Vertical airflow direction range control
To prevent draft, change the setting to "Upward" (01).
Note that the airflow in certain usage conditions may leave the ceiling dirty. In such cases, the use
of the optional Panel spacer (UTG-BKXA-W) is recommended.
5) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number Setting value Setting description Factory setting
23
00 Standard
01 Upward
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C
Ceiling
Swing scope (standard)
Swing scope (upward)