8-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢
Indoor unit
A twisted pair cable (22 AWG)should be used. Maximum length of cable is 82 ft (25 m).
Output voltage: High DC 12 V ±2 V, Low 0 V.
Permissible current: 50 mA
For details, refer to
"Setting of external input and output" on page 21.
When indicator, etc. are connected directly
Example: Function setting number 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected device
+
-
When connecting with a device equipped with a power supply
Example: Function setting number 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected device Relay
(Operation status)
-
+
- 19 -
8-2. External output
8. External input and output
WALL MOUNTED
ASUG09-12LMAS
WALL MOUNTED
ASUG09-12LMAS