8-3. Setting of external input and output
Indoor unit
Input
Connection point Function setting number 46 Function
CN46
00 Operation/Stop mode 1 (R.C. enabled)
01 (Setting prohibited)
02 Forced stop mode
03 Operation/Stop mode 2 (R.C. disabled)
Output
Connection point Function setting number 60 Function
CN47
00 Operation status
01 to 04 Cooling thermostat On
05 Heating operation
06 Operation/Stop
07 to 08 Cooling thermostat On
09 Error status
10 Indoor unit fan operation status
11 External heater output
- 21 -